Controllable
Electric Reactors
Consortium
of Russia and the CIS
(CERC)
CERC/ExpandingEdge

Single-Phase MCR as Automatic Ground-Fault Neutralizer (Patented)

 

APPLICATION FIELD AND PURPOSE:

Neutralizes automatic ground-fault capacitive current in electrical networks with isolated neutral.

Prevents transition of single-phase ground faults to multi-phase short circuits.

COMPLETE EQUIPMENT:

As shown in the diagram below,
  • Electric reactor (2) with built-in thyristor converter, controlled by self-magnetization– 1 unit;
  • System for ground fault capacitive current measurement and for automatic adjustment of reactor current (1) – 1 unit.
  • Overvoltage limiter (5)– 1 unit.
  • Optional 3-phase network connection filter (4)– 1 unit.
  • Optional grounding transformer and voltage transformer (3)– 1 unit.

PRINCIPLES OF OPERATION:

In the figure shown, an automatic adjustment and control system (1) defines the expected value of ground fault capacitive current and sends a control signal to the single-phase MCR converter (2), thus providing reactor control.

When a ground fault occurs, the reactor reduces the resulting current value at the damage point to a negligible value. The reactor switches to compensation mode without requiring intervention by maintenance personnel. The adjustment process is fully automatic.

Under normal operating conditions, the single-phase MCR is not saturated, eliminating resonance overvoltages in the neutral line.

This reactor may also be used in 3-phase electric grids and consumers. In this case, a filter (4) for connection of the reactor to the 3-phase network is supplied with the reactor.

MAIN TECHNICAL DATA:

Rated power: 190 kVA 300 kVA 480 kVA 840 kVA
Rated voltage: 11/3 kV;
6.6/3 kV
11/3 kV;
6.6/3 kV
11/3 kV;
6.6/3 kV
11/3 kV
Frequency: 50(60) Hz 50(60) Hz 50(60) Hz 50(60) Hz
Compensation current control range (continuous mode): 2.5 to 25,
4.25 to 42.5
4.0 to 40,
6.6 to 60
6.3 to 63,
10.5 to 105
11 to 105
2 hour compensation mode current: 30 A
50 A
48 A
80 A
76 A
126 A
132 A
Residual current, phase-to-ground short circuit: 2.0 A
2.75 A
2.75 A
3.5 A
3.5 A
5.0 A
5.0 A
Dimensions: 1030x1165
x1690 mm
1100x1235
x1710 mm
1130x1410
x1750 mm
1160x1980
x1950 mm
Weight: 1200 kg 1750 kg 2000 kg 3500 kg
Oil weight: 250 kg 350 kg 450 kg 1000 kg
Special orders: Any power up to 2.5 MVA,
Any voltage up to 35 kV.

AUTOMATIC ADJUSTMENT & CONTROL SYSTEM

Supply voltage: 220 V
Frequency: 50(60) Hz
Consumed power: 300 W
Signal memory time: 20 hrs
Weight: 3.2 kg
Dimensions: 260x270x160 mm

EFFICIENCY OF USE

Use of the single-phase MCR results in reduction of ground faults by a factor of three and their full containment in overvoltage-caused insulation breakdown.

This device provides intact operation and increased lifetime of electric equipment.

Average cost recovery has been achieved in about 2.5 years.

TOTAL COST OF OWNERSHIP (TCO)

As a percentage of ex-works price TCO is as follows:

Delivery (brokerage, customs, etc.) 5 to 10%
Construction and installation Average 25%
(depending on location)
Operation and maintenance 4% per annum

In other words, the TCO of an MCR is similar to that of a transformer of the same class.

MEAN TIME BETWEEN FAILURE (MTBF)

CERC guarantees its MCR's for a lifetime of not less than 25 years, with first major maintenance guaranteed not to occur within 12 years.

Each phase of the reactor, its grounding filter and current-distortion corrector (an LC filter) are guaranteed for a minimum of 3 years.

The power control system, including the transformer with its built-in thyristor subsystem is guaranteed for one year. The average practical time to failure of smaller MCR's is 5 years.

 

CERC/ExpandingEdge